GE Industrial Solutions EntelliPro ES User Manual

Page 48

Advertising
background image

CHAPTER 2: INSTALL ATION/CONFIGURATION

EPOS MOTOR MANAGEMENT SYSTEM- INSTRUCTION MANUAL

2.23

 

 

 

For EntelliPro ES3 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98 is mapped to external supervision

- active low.

Input 97 is mapped to control circuit feedback

- active low

Input 96 is mapped to main circuit feedback

- active low

Input 95 is mapped to emergency stop

- active low

Input 94 is mapped to external supervision

- active high

Input 93 is mapped to safety circuit

- active low


Output 41 is mapped to contactor 1
Output 43 is mapped to ON1 feedback
Output 45 is mapped to failure

For EntelliPro ES5 types:

Input 99 is mapped to contactor 1 feedback

- active high

Input 98

- not used

Input 97 is mapped to reset alarm

- active high

Input 96 is mapped to drawer in test mode

- active high

Input 95 is mapped to drawer in operation mode

- active high

Input 94 is mapped to main circuit feedback

- active low

Input 93 is mapped to control circuit

- active low

Input 11 is mapped to command OFF

- active low

Input 12 is mapped to command ON

- active high

Input 13

- not used

Input 14 is mapped to external fault

- active high

Input 15 is mapped to external supervision

- active low

Input 16 is mapped to emergency stop

- active low

Input 17 is mapped to safety circuit

- active low

Input 18 is mapped to mode switch local

- active high

Input 19 is mapped to mode switch remote

- active high

Output 41 is mapped to contactor 1

Output 43 is mapped to ATEX redundancy contactor

Output 45 is mapped to warning (high priority) and failure - relay flashing (low priority)

Output 22 is mapped to local control

Output 23 is mapped to ON1 feedback

Output 24 is mapped to warning

Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)

Output 26 is mapped to failure

Advertising