EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

Variable

Description

Min

Max

Step

Units

Scale

Format

Default

63

16 bit

Reset Configuration

BIT0 - Overload

 

 

 

BIT1 - Phase Loss

 

BIT2 - Gf

 

BIT3 - UnbalancedLoad

 

BIT4 - Thermistor

 

BIT5 - Emergencystop

 

BIT6 - LimitSwitch

BIT7 - SafetyCircuit

BIT8 - MainCircuit

BIT9 - ControlCircuit

BIT10 - SwitchPosition

BIT11 - UnderLoadCurrent

BIT12 - OverLoadCurrent

BIT13 - ExternalSupervision

BIT14 - LongStart

BIT15 - SoftStarter

Feedback Failure
MCC B2

 

1 = Manual Reset required

0 = Auto Reset

Note: The number of Auto reset is depending

on the value set on holding register 45.

 

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

1 = Manual Reset required

0 = Auto Reset

0

65535

1

0

 

Unsigned

Integer

255

64

16 bit

Protection / Input Configuration

 

BIT0 - Overload

 
 

 

BIT1 - Phase Loss

 

BIT2 - Ground fault

 

BIT3 - Unbalanced Load

 

BIT4 - Thermistor

 

BIT5 - Emergency stop

 

BIT6 - Limit Switch

BIT7 - Safety Circuit

BIT8 - Main Circuit

BIT9 - Control Circuit

BIT10 - Contactor Feedback

BIT11 - Under Load Current

BIT12 - Overload Current

BIT13 - External Supervision

BIT14 - Long Start

BIT15 - Typical Specific

Protection and Input Alarm/Fault(trip)

Configuration

1 = Warning - (Overload protection is

configured as an alarm)

0 = Failure (Trip) - (Overload protection is
configured as a Failure / Trip)

 

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

1 = Warning

0 = Failure (Trip)

0

65535

1

 

 

Unsigned

Integer

65280

65

16 bit

Device Error Reset Configuration

Bit0 - Reset Configuration of device Error

 

 

Bit1 - Device Error Configuration

Bit2 - 15 - Free

 

Bit0 = 1 ->Manual reset is required

0 = Auto reset of error, 0 must be under 1

 

Bit = 1 ->Warning

0 = Failure (Trip), 0 must be under 1

0

3

1

 

 

Unsigned

Integer

2