GE Industrial Solutions EntelliPro ES User Manual

Page 155

Advertising
background image

4.18

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

CHAPTER 4: COMMUNICATION

 

 

 

 

 

Holding

Register

Modbus

Size

 

Variable

 

Description

Min

Max

Step

 

Units

 

Scale

 

Format

Default

15

16 bit

Ground Fault Delay

 

10

100

10

msec

GF Dly

Setting

x 10

10 =

100msec

Unsigned

Integer

10

16

17

32 bit

Analog Output Value

If analog output is set to 0-20mA - the current
set on this register corresponds to 20 mA.

If analog is set to 4-20mA - the current set on

this register corresponds to 20 mA.

10

520000

1

mA

10 mA

Example:

10 =

100mA

100

= 1A

Unsigned

Integer

20

18

16 bit

Overload / Locked Rotor / Stalled Rotator

Current threshold

100

800

 

%

Irated

(motor

load) * %

Unsigned

Integer

20

19

16 bit

Start Phase Threshold

If a current exceed this threshold by a pre-

defined timer set by Timer2, an alarm or fault
will occur.

100

800

 

%

Irated

(motor

load) * %

Unsigned

Integer

20

20

16 bit

Under current Threshold

If a current falls below this threshold by a

pre-defined timer set by Timer15, an alarm or

fault will occur.

0 = disabled

1

100

 

%

Irated

(motor

load) * %

Unsigned

Integer

20

21

16 bit

Typical Specific Threshold

Current threshold used on actuator, solenoid

valve, start-delta typicals

1

200

 

%

Irated

(motor

load) * %

Unsigned

Integer

20

26

16 bit

Timer1

Maximum switch time (contactor feedback)

allowed

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

27

16 bit

Timer2

Motor start time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

28

16 bit

Timer3

Modbus Bus failure OFF/ON delay time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

29

16 bit

Timer4

Maximum switch time (current flow)

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

30

16 bit

Timer5

Minimum switch over time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

31

16 bit

Timer6

Profibus Class 1 Bus failure OFF/ON delay time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

32

16 bit

Timer7

Blocked motor time/Overload/Locked Rotor/
Stalled Rotator

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

33

16 bit

Timer8

Maximum Star time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

34

16 bit

Timer9

Star / Delta Switch over time

1

65535

1

msec

Setting *

10msec

Unsigned

Integer

1

35

16 bit

Timer10

Maximum switch time limit switch

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

36

16 bit

Timer11

Maximum soft starter time

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

37

16 bit

Timer12

Maximum soft stop time/ max breaker ON

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

38

16 bit

Timer13

Applicable to custom logic only

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

39

16 bit

Timer14

Applicable to custom logic only

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

40

16 bit

Timer15

Undercurrent delay

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

41

16 bit

Timer16

Start Attempt

1

65535

1

msec

Setting *

100 msec

Unsigned

Integer

1

42

16 bit

Count1 (Not used in EntelliPro ES retrofit
version)

Applicable to custom logic only

1

65535

1

 

 

Unsigned

Integer

1

43

16 bit

Count2 (Not used in EntelliPro ES retrofit
version)

Applicable to custom logic only

1

65535

1

 

 

Unsigned

Integer

1

44

16 bit

Count3 (Start Attempt Counter in V5)

Number of start attempts allowed within a
specified time interval set by timer16

Example:

Timer16 is set 10 secs -

Count3 = 3

3 starts are allowed in 10 seconds interval

1

40

1

 

 

Unsigned

Integer

10