CHAPTER 2: INSTALL ATION/CONFIGURATION

2.54

EP OS MOTOR MANAGEMENT SYSTEM – INSTRUCTION MANUAL

 

 

Output 41 is mapped to breaker ON

Output 43 is mapped to breaker OFF

Output 45 is mapped to reset

Output 22 is mapped to local control

Output 23 is mapped to ON1 command (start)

Output 24 is mapped to warning

Output 25 is mapped to drawer ready switch (high priority) and identification –relay flashing (low priority)

Output 26 is mapped to failure

Refer to Tables 2-6 and 2-7 for the complete input, output, timer and control configurations of breaker control
motor starter.

Figures 2-22 and 2-23 show typical breaker control motor starter diagrams for EntelliPro ES3 and EntelliP

ro ES.

feedback alarm is disabled, the Breaker status will be ON irrepective of the breaker feedback hardwired input.

NOT the Breaker auxiliary switch status (Breaker feedback input). For example, if the ON command is sent and

NOTE:

I

nterpoling CTs are required for higher than 630Amps system.

CAUTION:

If the Breaker feedback alarm is disabled, the EntelliPro ON/OFF command will be the Breaker status


Figure 2-22: EntelliPro ES3 Breaker control starter wiring diagram