Parameter descriptions (by parameter group) – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 124

Advertising
background image

5–14

Programming Parameters

Publication 1397-5.0 — June, 2001

This section provides a list of 1397 parameters sorted into their
respective parameter groups with their associated default values,
Display/Drive units, description and group designation and any
applicable enums.

Tunable – Parameter can be changed while the drive is running.
Configurable – Parameter can only be changed when the drive is
not running.

To help differentiate parameter names and display text from other
text in this manual, the following conventions will be used:
D Parameter names will appear in [Brackets]
D Display text will appear in “quotes”.

METERING

[Anlg In 1] — P.001

Analog reference 1 value measured by the
drive after all hardware and software scaling.

Display/Drive Units:

RPM

Group:

Metering

Parameter Type

Output

Factory Default

0

Minimum Value

–5369

Maximum Value

5369

[Anlg In 2] — P.002

Analog reference value measured by the
drive after all hardware and software scaling.

Display/Drive Units:

RPM

Group:

Metering

Parameter Type:

Output

Factory Default

0

Minimum Value

–5369

Maximum Value

5369

[Anlg In 3] — P.003

Only used if the I/O Expansion kit is installed.

The value representing analog input 3
(terminals 50 and 51 on the I/O Expansion
board) after gain and zero have been applied.
Refer to the I/O Expansion Inputs (Fig. A.2)
block diagram for additional information.

Display/Drive Units:

CNTS

Group:

Metering

Parameter Type

Output

Factory Default

0

Minimum Value

–5369

Maximum Value

5369

Parameter Descriptions