Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 145

Advertising
background image

5–35

Programming Parameters

Publication 1397-5.0 — June, 2001

REFERENCE SET

[Preset Speed 1, 2 and 3] — P.87, P.88 and P.89

These parameters set up to three preset
speed references when the Regulator Type
jumper (J15 on the regulator board) is set for
the speed/voltage control loop or current
reference when J15 is set to current.

Display/Drive Units:

%FLA

Parameter Range:

0 to [Maximum Current] — %FLA

Default Setting:

150 %FLA

Parameter Type:

Tunable

Group:

Reference Set

Display/Drive Units:

RPM
OR

Parameter Range:

[Min Process Speed] to [Max Process Speed] RPM

Default Setting:

250 RPM

Parameter Type:

Tunable

Group:

Reference Set

Factory Default:

250

Minimum Value:

Min Process Speed

Maximum Value:

Max Process Speed

[Ref 1 Source] — P.090

Selects the source of external reference 1

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Anlg In 1
1 = Speed Pot
2 = MOP Output
3 = Anlg In 3
4 = Anlg In 4
5 = Frequency In
6 = Adapter 1
7 = Adapter 2
8 = Adapter 3
9 = Adapter 4
10 = Adapter 5
11 = Adapter 6
12 = Preset 1
13 = Preset 2
14 = Preset 3

Parameter Type:

R & W

Group:

Reference Set

Factory Default:

0

Minimum Value:

0

Maximum Value:

14