The following tables list the recommended AC line and DC armature
fuses for the Drive. The armature fuse is required only for
regenerative Drives.

Standard models are shipped with the appropriate fuses.

You must select the correct replacement fuse type from Tables 2.E
and 2.F.

Table 2.E
AC Line Fuses

AC Line Fuse (1FU, 2FU, 3FU)
HP at 230 V AC

HP at 380 V AC

HP at 415 V AC

HP at 460 V AC

Fuse Rating (500 V)

Fuse Class

Manufacturer

1.5-5
7.5-10
15
20-30
40-60
75
100
125-150

2.4
12
24
48
120

2.8
13.8
27.6
55.2
138

3-10
15-20
30
40-60
75-125
150
200
250-300
400-600

40A
80A
90A
150A
300A
350A
600A
800A
600A (700V)
2 in parallel

XL50F
XL50F
XL50F
XL50F
XL50F
XL50F
XL50F
XL50F

A70QS600–4K

Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman

Gould

Table 2.F
DC Armature Fuses (Regenerative Drives Only)

DC Line Fuse (11FU)
HP at 230 V AC

A @ 380/415 V AC

HP at 460 V AC

Fuse Rating (700 V)

Fuse Class

Manufacturer

1.5
2
3
5
7.5
10
15
20-25
30
40
50
60
75

7
7
7
7
29
29
55
55
110
110
110
110
205

3
4
6
10
15
20
30
40-50
60
75
100
125
150

15A
20A
25A
35A
40A
50A
70A
125A
150A
200A
250A
300A
350A

XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F
XL70F

Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman
Bussman