5–32

Programming Parameters

Publication 1397-5.0 — June, 2001

ADV SETUP

[PLL Max Error] — P.071

Maximum allowable change in line period per
AC line cycle. This input should only be
increased when drive power is supplied by a
source that cannot maintain a suitable fixed
frequency output (such as an alternator) to
prevent line synchronization-related faults.

Display/Drive Unitse:

uSEC

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

2

Minimum Value:

2

Maximum Value:

1000

[Spd LeadLag Freq] — P.072

If Lead/Lag is selected in [Spd Leadlag
Type]
, this parameter represents the low lead
frequency. If [Spd Leadlag Type] is set to
Bypass, this parameter has no effect. If
Lag/Lead is selected, it represents the low lag
frequency.

Display/Drive Units:

RD/S

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

100

Minimum Value:

1

Maximum Value:

3490

[Spd LeadLag Rato] — P.073

Sets the ratio of low to high break frequencies
for the lead/lag block. For example, if this
parameter is set to 10, the high break
frequency will be 10 times the low break
frequency — specified by [Spd Leadlag
Freq]
. If [Spd Leadlag Type] is set to
Bypass, this parameter has no effect.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

2

Minimum Value:

2

Maximum Value:

20

[Spd LeadLag Type] — P.074

Determines if the lead/lag block will act upon
the speed loop feedback signal. If On, the
lead/lag block is bypassed and the feedback
signal is used directly by the speed loop
summing junction.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Lead/Lag
1 = Bypass
2 = Lag/Lead

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

1

Minimum Value:

0

Maximum Value:

2