4–4

Start–Up and Adjustment

Publication 1397-5.0 — June, 2001

Figure 4.2
Control TransformerTap Settings

400-600 HP @ 460 VAC

400 & 500 HP

SB

H1

H2

H3

H4

X3

X2

X1

F

600 HP

RV

H1

H2

H3

H4

X3

X2

X1

F

Primary

460V

Secondary

115V

460V

Primary

Secondary

115V

183

182

188A

189A

188A

189A

183

182

Converting a 300 HP 1397 Drive from 460 to 230 VAC Line Input

Unlike lower horsepower units, 200-300 HP 1397 Drives can be
converted from 460VAC input to 230 VAC input without the use of a
conversion kit. To convert a 300 HP Drive perform the following
steps:

• Disconnect and lock out all incoming power to the Drive.
• Disconnect the jumpers between H2 and H3 on the control

transformer as shown in Figure 4.3.

• Use the jumpers that were removed to connect H1 to H3 and H4

to H2, as shown in Figure 4.3.

• Reconnect power to the Drive.
• Access parameter 51 [Nominal AC Volt], Set the value to 230.
Converting a 600 HP 1397 Drive from 460 to 230 VAC Line Input

Converting a 600 HP Drive from 460 to 230VAC input is NOT
recommended.

A 600 HP 1397 Drive operating off a 230VAC line input may not
have sufficient voltage for the field supply.