Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 58

Advertising
background image

2–40

Installation

Publication 1397-5.0 — June, 2001

7. Wiring the Output Circuits

The 1397 Drive contains 2 Analog Outputs and 3 Digital Outputs as
illustrated in Figure 2.30.
The Analog Outputs are fixed +/– 10 VDC outputs that are updated
every 20 ms by the Drive and are sent thru a 100 ms running
averaging filter within the drive.
ANALOG OUTPUT 1 is connected at terminals 24 and 25 and
[Anlg Out 1 Src] (P 145) determines which Drive testpoint is the
source selected.
ANALOG OUTPUT 2 is connected at terminals 25 and 26 and
[Analog Out 2 Src] (P. 148) determines which Drive testpoint is the
source selected.

The Digital Outputs indicate the present operating state of the
Drive and are connected as follows:
Terminals 27–28 – 1 = Running

0 = Not Running

Terminals 29–30 – 1 = Alarm active 0 = No alarms active
Terminals 31–32 – 0 = Fault active 1 = No faults active

Figure 2.30
Regulator Board Terminal Strip

Output Connections

24

25

26

ANALOG OUT 1

27

RUNNING

ANALOG OUT Common

ANALOG OUT 2

28

29

ALARM

30

31

FAULT

32