FEATURE SELECT

[AutoTune Fld Rng] — P.113

Set to the ratio of [Max Motor Speed] and
motor base speed = 1.00 when no field
weakening is used. Applies to speed loop
autotuning only. The higher the value, the
faster the motor speed.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Feature Select

Factory Default:

1.00

Minimum Value:

0.90

Maximum Value:

5.00

[AutoTune Stablty] — P.114

Selects the desired performance of the speed
loop after auto tuning. A higher value
decreases the speed loop’s response.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Feature Select

Factory Default:

25

Minimum Value:

10

Maximum Value:

100

[Stop Mode Type] — P.115

Selects stopping mode of the drive in
response to a Stop command. An open
“customer interlock” only causes a coast stop.
If the drive is configured as a current
regulator, only Coast/DB can be selected.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Ramp
1 = Curr Limit
2 = Coast/DB

Parameter Type:

Tunable

Group:

Feature Select

Factory Default:

2 (Coast/DB)

Minimum Value:

0

Maximum Value:

2

[Stop Speed Level] — P.116

Sets the threshold speed below which the
main contactor will automatically open after a
ramp stop or current limit stop is asserted.
This value should be less than or equal to
[Min Process Speed].

Display/Drive Units:

RPM

Parameter Type:

Tunable

Group:

Feature Select

Factory Default:

50

Minimum Value:

0

Maximum Value:

Max Process Spd