Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 167

Advertising
background image

5–57

Programming Parameters

Publication 1397-5.0 — June, 2001

OUTPUT CONFIG

[Anlg Out 3 Type] — P.152

Only used if the I/O Expansion kit is installed.

Selects the type of signal to be generated by
analog output 3 (terminals 54 and 55 on the
I/O Expansion board). This setting must
match the settings of jumpers J14 and J15 on
the I/O Expansion board.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = 0-10V
1 =

±10V

2 = 4 -20mA
3 = 10–50mA

Default Setting:

±10V

Parameter Type:

Configurable

Group:

Output Config

Factory Default:

1

Minimum Value:

0

Maximum Value:

3

[Anlg Out 4 Gain] — P.153

Adjusts analog output 4. Only used if I/O
Expansion kit is installed.

Display/Drive Units:

VDC

Parameter Type:

Tunable

Group:

Output Config

Factory Default:

1.000

Minimum Value:

0.500

Maximum Value:

1.300