1–5

Introduction

Publication 1397-5.0 — June, 2001

Service Conditions

Ambient Temperature

Chassis

55

_C (131_F) maximum

Cabinet

40

_C (104_F) maximum

Altitude

Chassis and Cabinet

3300 feet above sea level

Above 3300 feet

Derate 3% for every 1000 ft above
3300 ft up to 10000 ft.

Humidity

Chassis and Cabinet

5 to 95% non-condensing

Environment

The drive should be located in an area
that is free of dust, dirt, acidic or
caustic vapors, vibration and shock,
temperature extremes, and electrical or
electromagnetic noise interference.

Regulation

Tachometer Speed Regulation

Regulation Arrangement

Speed Change
with 95% Load

Change

Speed Change

from All other

Variables

Kit Model Number

Armature voltage regulation w/IR
Compensation

2-3 %

15%

Standard

Closed Loop

( DC Tach Feedback)

1%

2%

Standard

(Pulse Encoder Feedback )

1

( RD–120 Pulse Encoder FDBK)

1

0.01%

0.01%

1397 – PE

0.01%

0.01%

1397 PE

1

Optional pulse encoder feedback kit required.

Speed Change

Operator’s Speed Adjustment

0 to rated speed

Specification Speed Range

100:1 based on top speed and
tachometer

Drive Efficiency

Drive Only

98.6% (rated load and speed)

Drive and Motor

85% typical

Note: Typical percent shown depends on motor operating speed and frame size.

Power Ratings

Displacement Power Factor

88% typical (rated load and speed)

Note: Typical percent shown depends on motor operating speed and frame size.