Regulated Field Supply
The Regulated Field Supply (Fig. 4.6) allows the motor to run above
base speed (i.e. to operate in the constant horsepower range) by
weakening the motor field current. Prior to applying the regulated
field supply output to the DC motor’s field windings, the output
current must be adjusted so that it does not exceed the rated motor
field current. This procedure is described in the Regulated Field
Supply Kit Installation manual, Publication 1397-5.17.