5–55

Programming Parameters

Publication 1397-5.0 — June, 2001

OUTPUT CONFIG

[Anlg Out 2 Zero] — P.149

Removes any hardware-introduced offset
from the Analog 2 output signal at the
regulator board terminal strip.

Display/Drive Units:

Numeric

Parameter Type:

Tunable

Group:

Output Config

Factory Default:

0

Minimum Value:

–200

Maximum Value:

200

[Anlg Out 3 Gain] — P.150

Only used if the I/O Expansion kit is installed.

Adjusts analog output 3 (terminals 54 and 55
on the I/O Expansion board) to allow it to
produce a signal from 5.0 to approximately
13.0 V DC.

Display/Drive Units:

VDC

Parameter Type:

Tunable

Group:

Output Config

Factory Default:

1.00

Minimum Value:

0.500

Maximum Value:

1.300

This is typically used to adjust the 10 V full scale output to match the input voltage requirement of attached equipment. For example, this
parameter would be set to 0.800 to match the requirements of equipment that accepts a 0 to 8 V DC signal.

The outputs are only rated to 10 V DC, so gain adjust values greater than 1.000 might cause the analog output circuit to saturate.