Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 140

Advertising
background image

5–30

Programming Parameters

Publication 1397-5.0 — June, 2001

ADV SETUP

[Cur Loop RateLim] — P.064

Minimum allowable time for selected Current
Loop reference to change from zero to
[Maximum Current].

Display/Drive Units:

MSEC

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

40

Minimum Value:

1.000

Maximum Value:

100

[IR Compensation] — P.066

Sets the armature voltage compensation
value used when the drive is configured as a
voltage regulator. This parameter is also used
by the field current regulator to set the field
weakened threshold.

Display/Drive Units

% [Motor Arm Volts (P046)]

Group:

Advanced Setup

Factory Default:

0

Minimum Value:

0

Maximum Value:

50%

[Pos Current Lim] — P.067

Sets the highest amount of current (% motor
rated armature amps) for the forward bridge.
Used as a high limit for the speed loop PI
block output.

Display/Drive Units:

% FLA

Parameter Type:

Tunable

Group:

Advanced Set–Up

Factory Default:

150%

Minimum Value:

0

Maximum Value:

Max Setting of Param 040
Note: Setting of this parameter is limited by the setting of
Parm 040.

[Neg Current Lim] — P.068

Note: This parameter is only set for
regenerative drives.

Selects the highest amount of current (%
motor rated armature amps) for the reverse
bridge. Used as a low limit for the Speed
Loop PI block output.

Display/Drive Units:

% FLA

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

150%

Minimum Value:

0

Maximum Value:

200%