Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 139

Advertising
background image

5–29

Programming Parameters

Publication 1397-5.0 — June, 2001

ADV SETUP

[Arm Voltage Zero] — P.060

Used to remove any hardware-introduced
offset from the armature voltage signal. In
most cases, this input will be set to zero volts.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

0

Minimum Value:

–200

Maximum Value:

200

ATTENTION: The incorrect setting of this parameter can cause an
overspeed condition. This parameter must be set by a qualified person
who understands the significance of setting it. Set the value of this
parameter accurately per your application requirements. Failure to
observe this precaution could result in bodily injury.

!

[Cur Loop K Fdbk] — P.061

Current Loop Feedback gain adjustment. In
most cases, this input will be set for unity
gain. The range of this input may be affected
by the software scaling factor calculated by
the drive. Typically, it will be 1.000.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

1.000

Minimum Value:

1.000

Maximum Value:

1.100

[Cur Lp Lead Freq] — P.062

Lead break frequency for the Current Loop.

Display/Drive Units:

RD/S

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

100

Minimum Value:

10

Maximum Value:

500

[Cur Loop Kp] — P.063

Proportional gain for the Current Loop.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

0.250

Minimum Value:

0

Maximum Value:

4.000