The HIM displays the correct position of the jumper under the
Diagnostics menu [J18 Arm Fdbk Res] (P.183). Verify this jumper
setting before performing the self-tuning procedure.

Table 4.J lists the standard 1397 I/O input points indicating those
hardware inputs which are required for Drive operation. Some of
these signals may be generated by the terminal strip or a SCANport
device or HIM or both. These signals are identified in the table by
the column labeled “Alternate Control Source”.

NOTE: Required signals MUST be correctly wired to the terminal
strip for proper Drive operation, and cannot be masked. Signals that
are not required may be “masked off” for exclusive control by a
SCANport device or HIM. Masking parameters are described in
detail in Chapter 5: Programming Parameters.

IMPORTANT: Regulator Board terminal Strip Inputs 3, 8, 9, 12 and
13 must be closed for the Drive to be ready.

Table 4.J
Standard I/O Functions

I/O Point

Required

Contact Sense

No
YES
No
No
No

YES

YES

No

Yes

Yes

No

No

No

SCANport/HIM
SCANport/HIM
SCANport/HIM
SCANport/HIM
SCANport/HIM

None

None

SCANport/HIM

None

None

Scanport/HIM

Scanport/HIM

None

Start when CLOSED
Stop when OPEN
Jog when closed
Forward = Open Rev = Closed
Selects Analog Ref 2 when Open
Selects Analog Ref 1 when Closed
Opens AC or DB Contactor (if installed)
when OPEN Motor Coasts to Stop
Opens AC contactor when OPEN –
motor coasts to stop
Resets fault / acknowledges alarm
when CLOSED
When OPEN activates warning
Motor will still run.
Opens AC contactor when OPEN –
motor coasts to stop
External speed reference selected
when REF SELECT CLOSED
External speed reference selected
when REF SELECT OPEN

Run
STOP
Jog
Rev/Fwd
Reference Select

Coast to Stop

Customer
Interlock
Fault/Alarm Reset

Brush Wear

Motor Thermostat

Analog Ref 1

Analog Ref 2

Analog Tachometer

Alternate Control Source

Active Function

NO
NC
NO
NO
NO

NC

NC

NO

NC

NC

Analog

Analog

Analog

Input for DC (analog) tachometer