5–60

Programming Parameters

Publication 1397-5.0 — June, 2001

OUTPUT CONFIG

[Dig Out 2 Src] — P.157

Only used if the I/O Expansion Kit is installed.

Selects the signal used to drive digital output
2 (terminals 68 and 69 on the I/O Expansion
board).

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Monitor1 Out
1 = Monitor2 Out
2 = In Cur Limit
3 = Drive Ready

Parameter Type:

Configurable

Group:

Output Config

Factory Default:

1

Minimum Value:

0

Maximum Value:

3

ATTENTION: This output is intended for use as an indication. DO
NOT use this as a control source. If it is used as a control source, a
dangerous condition can result. Failure to observe this precaution can
result in severe bodily injury or loss of life.

!

[Dig Out 2 Type] — P.158

Only used if the I/O Expansion Kit is installed.

Selects whether digital output 2 (terminals 68
and 69 on I/O Expansion board) is normally
open or normally closed.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Normal Open
1 = Normal Closed

Parameter Type:

Configurable

Group:

Output Config

Factory Default:

0

Minimum Value:

0

Maximum Value:

1

ATTENTION: On a power cycle or reset, the contact is held at
normally open until the drive software is initialized. Make sure
that this condition does not result in a dangerous situation for
your application. Failure to observe this precaution can result
in severe bodily injury or loss of life.

!

If [Normal Open] is selected, digital output 2 is open when the signal is off and closed when it is on.

If [Normal Closed] is selected, digital output 2 is closed when the signal is off and open when it is on.

[Freq Out Scale] — P.159

Only used if the I/O Expansion kit is installed.

The frequency generated when the signal
driving the frequency output is at full scale.

For example, if [Freq Out Source] is set to
[Cur Lp Fdbk], the frequency specified by
this parameter is output when the armature
current is at [Maximum Current]
[Maximum Current] is used as the basis for
current minor loop scaling.

Display/Drive Units:

kHz

Parameter Type:

Configurable

Group:

Output Config.

Factory Default:

250.0 kHz

Minimum Value:

2.0 kHz

Maximum Value:

250.0 kHz

Refererence Parameters:

[Freq Out Source] — P.160
[Maximum Current] — P.040