2–37

Installation

Publication 1397-5.0 — June, 2001

Regulator Board Terminal Strip
24VDC Thermostat/Brush Wear Circuit

12

13

14

BRUSH WEAR

MOTOR THERMOSTAT

+24V

115VAC Option Board CON 2
115VAC Thermostat/Brush Wear Circuit

12

13

14

BRUSH WEAR

MOTOR THERMOSTAT

115V HI

Figure 2.26
Motor Thermostat/Brush Wear Wiring

The contacts of the motor thermostat and Brush Wear must be N.C.
The Drive interprets a voltage at Terminals 12 & 13 as a normal
expected condition. This input CANNOT be masked.

4. Wiring the Fault/Alarm Reset Circuit

This input clears fault and/or alarm indicators and resets the circuit.
As shown in Figure 2.27 the Fault/Alarm Reset circuit requires a
N.O. operator device that closes to cause a reset. This input can be
masked using the [Fault Reset Mask] (P. 205) or [Logic Mask]
(P. 207).

Regulator Board Terminal Strip
24VDC Fault/Alarm Reset Circuit

10

11

Fault/Alarm Reset

+24VDC

115VAC Option Board CON 2
115VAC Fault/Alarm Reset Circuit

10

11

Fault/Alarm Reset

+115VAC

Figure 2.27
Fault/Alarm Wiring