FEATURE SELECT

[Monitor 1 Source] — P.104

Selects the signal that drives monitor 1.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Cur Lp Fdbk
1 = Spd Lp Fdbk
2 = Spd Ramp Out
3 = Spd Ramp In
4 = Spd Src Out

Parameter Type:

Configurable

Group:

Feature Select

Factory Default:

1 (Spd Lp Fdbk)

Minimum Value:

0

Maximum Value:

4

Monitor 1
Output
(P13)

To I/O
Expansion
Outputs
Block Diagram

COMPARE

A

B

Monitor 1 Delay
(P103)

Start/Stop

Delay Time

TIMER

A > B

ABS

Monitor 1 Level
(P105)

Cur Lp Fdbk

Spd Lp Fdbk

Spd Ramp Out

Spd Ramp In

Spd Src In

Current Loop
Feedback Average

From Speed Loop Block Diagram

From Speed Reference
Ramp Block Diagram

From Speed Reference
Source Block Diagram

[Monitor 1 Level] — P.105

The threshold for level detector 1. Refer to
the Level Detectors block diagram (Fig.
A.12) for additional information.

When the absolute value of the signal driving
monitor 1 is

≥ this threshold, the associated

timer starts. If the input signal is < this
threshold, the timer is immediately reset and
the level detector output is set to off.

Display/Drive Units:

%

Default Setting:

10.0%

Parameter Type:

Tunable

Group:

Feature Select

Factory Default:

10.0%

Minimum Value:

0.1%

Maximum Value:

100.0%

The parameter range for the level detector is automatically rescaled for speed or current based on the input selected by [Monitor 1 Source]. If
[Cur Loop Fdbk] is selected for [Monitor 1 Source], the parameter range is 0.1 to [Maximum Current]. For any other [Monitor 1 Source]
settings, the parameter range is 0.1 to 100.0%.