Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 143

Advertising
background image

5–33

Programming Parameters

Publication 1397-5.0 — June, 2001

ADV SETUP

[Spd Lp Lag Freq] — P.075

Lag break frequency for the lag block. If [Spd
Lp Lag Type]
is set to Bypass, this
parameter has no effect.

Display/Drive Units:

RD/S

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

1.00

Minimum Value:

0.01

Maximum Value:

69.81

[Spd Lp Lag Type] — P.076

Determines if the lead/lag block will act upon
the speed loop feedback signal. If On, the
lead/lag block is bypassed and the feedback
signal is used directly by the speed loop
summing junction.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Lag 1 = Bypass

Default Setting:

Bypass

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

1

Minimum Value:

0

Maximum Value:

1

[Spd Lp Lead Freq] — P.077

Speed loop PI block lead frequency. A setting
of 0.00 allows proportional-only speed loop
control.

Display/Drive Units:

RD/S

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

3.00 rad/sec

Minimum Value:

0 rad/sec

Maximum Value:

141.37 rad/sec

[Spd Loop Kp] — P.078

Speed loop PI block proportional gain.
Refer to Fig A.7, Speed Loop Block Diagram
for more information.

Display/Drive Units:

Parameter Type:

Tunable

Group:

Advanced Setup

Factory Default:

4.40

Minimum Value:

0.10

Maximum Value:

128.0

[Tach Loss Angle] — P.079

Allows setting of Armature Delta firing angle
before a Tach Loss fault will be generated.

Display/Drive Units:

Degrees

Parameter Type:

Configuration

Group:

Advanced Setup

Factory Default:

109

Minimum Value:

0

Maximum Value:

127