5–36

Programming Parameters

Publication 1397-5.0 — June, 2001

REFERENCE SET

[Ref 2 Source] — P.091

Selects the source of external reference 2.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Anlg In 1
1 = Speed Pot
2 = MOP Output
3 = Anlg In 3
4 = Anlg In 4
5 = Frequency In
6 = Adapter 1
7 = Adapter 2
8 = Adapter 3
9 = Adapter 4
10 = Adapter 5
11 = Adapter 6
12 = Preset 1
13 = Preset 2
14 = Preset 3

Parameter Type:

R & W

Group:

Reference Set

Factory Default:

1

Minimum Value:

0

Maximum Value:

14

[Jog Acc/Dec Time] — P.092

Sets the time it takes the jog reference circuit
to reach [Jog Reference (P.093)] from zero.
Smaller changes in speed take proportionally
less time.

The [S-Curve Rounding] parameter does
not affect the setting of this parameter.

Display/Drive Units:

SEC

Parameter Type:

Tunable

Group:

Reference Set

Factory Default:

3.0

Minimum Value:

0.1

Maximum Value:

300.0

[Jog Reference] — P.093

The normal operating speed while the drive is
jogging.

Display/Drive Units:

RPM

Parameter Type:

Tunable

Group:

Reference Set

Factory Default:

250

Minimum Value:

0

Maximum Value:

Max Process Speed

ATTENTION: This drive can operate at and maintain zero speed when
this parameter is set to zero. The user is responsible for assuring safe
conditions for operating personnel by providing suitable guards, audible
or visual alarms, or other devices to indicate that the drive is operating at
or near zero speed. Failure to observe this precaution could result in
severe bodily injury or loss of life.

!