Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 176

Advertising
background image

5–66

Programming Parameters

Publication 1397-5.0 — June, 2001

DIAGNOSTICS

[J11 Tach V Scale] — P.180

Position in which to set J11 hardware jumper
based on the values of [Max Motor Speed]
and [Anlg Tach V/1000].
This is a READ ONLY parameter. Set
Jumper J11 to the drive determined value that
is displayed.

Display/Drive Units:

Numeric/Text

Parameter Range:

Low, High

Group:

Diagnostics
Read Only

Factory Default:

0

Minimum Value:

–1920

Maximum Value:

1920

[J14 Tach V Range] — P.181

Position in which to set J14 hardware jumper
based on the values of [Top Speed] and
[Analog Tach V/1000].
This is a READ ONLY parameter. Set
Jumper J14 to the drive determined value
that is displayed.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Low
1 = High

Group:

Diagnostics
Read Only

Factory Default:

0

Minimum Value:

0

Maximum Value:

1

ATTENTION: The drive will not operate at the correct speed if this
jumper is not set to the correct position. Failure to observe this
precaution could result in damage to, or destruction of the equipment.

!

[J15 Reg Type] — P.182

Indicates the position of hardware jumper J15
Regulator Type, which selects the type of
regulator: Speed/Voltage or Current/Torque.
This jumper is only read at power-up.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Spd/Voltage
1 = Curr/Torque

Group:

Diagnostics
Read Only

Factory Default:

0

Minimum Value:

0

Maximum Value:

1

[J18 Arm Fdbk Res] — P.183

Indicates the required burden resistor position
to scale armature current feedback based on
the values of [CT Turns Ratio], [Maximum
Current]
and [Motor Arm Amps].

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = J18 Error
1 = Position 1
2 = Position 2
3 = Position 3
4 = Position 4

Group:

Diagnostics

Factory Default:

0

Minimum Value:

0

Maximum Value:

4