5–94
Programming Parameters
Publication 1397-5.0 — June, 2001
Process PI
[OCL Ramp Time] — P.298
The ramp time for the outer control loop
reference. Sets the minimum amount of time
for the OCL S-curve output to change from 0
to full scale and vice versa. If set to 0.0, the
ramp block is bypassed.
Note: If the ramp block is bypassed, rapid
speed change can result.
Display/Drive Units:
SEC
Parameter Type:
Tunable
Group:
Process PI
Minimum Value:
0.0 sec.
Factory Default:
10.0 sec.
Maximum Value
300.0 sec.
[OCL Reference] — P.299
The reference value for the outer control loop.
Displayed in OCL user units.
Display/Drive Units:
CNTS
Parameter Type:
Tunable
Group:
Process PI
Minimum Value:
–4095
Factory Default:
0
Maximum Value
4095