Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 206

Advertising
background image

5–96

Programming Parameters

Publication 1397-5.0 — June, 2001

Process PI

[OCL Trim Range] — P.302

The trim range for the outer control loop. This
specifies the amount of control the outer
control loop output signal has on the
speed/voltage loop reference. It is set as a
percentage of [Max Process Speed]. Refer
to the [OCL Lead Freq] block diagram for
additional information.

Display/Drive Units:

%

Parameter Type:

Tunable

Group:

Process PI

Minimum Value:

0.0%

Factory Default:

0.0%

Maximum Value

100.0%

[OCL Enable] — P.303

Parameter that controls enabling or disabling
the OCL when [OCL Enable Src] is set to
“Register”.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Enable
1 = Disable

Default Setting:

Disable

Parameter Type:

Tunable

Group:

Process PI

Minimum Value:

0

Factory Default:

1

Maximum Value

1

[OCL Fdbk Reg] — P.304

Allows Outer Control Loop Feedback value to
be entered (via Datalink also) when OCL
Fdbk Source (P. 290) is set to “Register”.
This parameter’s value is not saved through a
power cycle., it is reset to zero at powerup.

Display/Drive Units:

Cnts

Parameter Range:

+/– 4095

Default Setting:

0

Parameter Type:

Tunable

Group:

Process PI

Minimum Value:

0

Factory Default:

–4096

Maximum Value

+4095