Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 133

Advertising
background image

5–23

Programming Parameters

Publication 1397-5.0 — June, 2001

SETUP

[Decel Time] — P.038

Selects the time it takes to decelerate from
[Max Motor Speed] to 0. Smaller changes in
speed take proportionately less time.

If [Trim Mode Type] is set to [Proportional],
the actual time to decelerate might be
modified by [Draw Percentage Out]. Refer to
the Speed Reference Ramp Block illustration
(A.4) for more information.

Display/Drive Units:

SECS

Group:

Setup

Type:

Tunable

Factory Default:

5.0

Minimum Value:

0.1

Maximum Value:

300.0

[Feedback Type] — P.039

Selects the type of feedback signal that is
used for the speed/voltage loop.

0 = Arm Volt
1 = DC Tach
2 = Pulse Encoder
3 = AC Tach

Display/Drive Units:

Numeric

Group:

Setup

Type:

Configurable

Factory Default:

0 (Arm Volt)

Minimum Value:

0 (Arm Volt)

Maximum Value:

3 (AC Tach)

[Maximum Current] — P.040

The highest amount of current (positive or
negative) for a given application. This input is
used as the basis of armature current scaling.
[Maximum Current] is limited to 200% of
[Motor Arm Amps].

Display/Drive Units:

% FLA

Group:

Setup

Type:

Configurable

Factory Default:

150

Minimum Value:

25

Maximum Value:

200

[Max Motor Speed] — P.041

[Max Motor Speed] is the highest normal
running speed of the motor. This parameter
scales the feedback device.

[Max Motor Speed] depends on several
factors:
D If there is no field weakening, the top

speed is typically the same as the motor
nameplate base speed.

D If there is field weakening, the top speed

is the same as the field weakened speed.
Top speed is typically more than the base
speed when field weakening is applied.

Display/Drive Units:

RPM

Group:

Setup

Type:

Configurable

Factory Default:

500

Minimum Value:

5

Maximum Value:

5000

ATTENTION: The incorrect setting of this parameter can cause an
overspeed condition. This parameter must be set by a qualified person
who understands the significance of setting it. Set the value of this
parameter accurately per your application requirements. Failure to
observe this precaution could result in bodily injury.

!

Advertising