3–7

Programming Terminal

Publication 1397-5.0 — June, 2001

Program and Display Modes

or

or

or

1. The Display and Program modes allow

access to the parameters for viewing or
programming.

A. From the Status Display, press Enter (or

any key). “Choose Mode” will be
shown.

B. Press the Increment (or Decrement) key

to show “Program” (or “Display”).

C. Press Enter.

D. Press the Increment (or Decrement) key

until the desired group is displayed.

E. Press Enter.

F. Press the Increment (or Decrement) key

to scroll to the desired parameter.

Choose Mode
Display

Choose Mode
Program

Choose Group
Metering

Anlg In 1
+0 RPM

or

Bit ENUMs

Masks
Logic Mask

Terminal Blk
X1111111

Bit ENUMS (16 character text strings) will
be displayed to aid interpretation of bit
parameters.

G. Select a bit parameter with the Increment

(or Decrement) keys.

H. Press the SELect key to view the ENUM

of the first bit. Pressing this key again
will move the cursor to the left one bit.

A blinking underline cursor will indicate
that you are in the Display mode or that a
Read Only parameter has been accessed.
A flashing character will indicate that the
value can be changed.

Individual bits of a Read/Write parameter
can be changed in the same manner.
Pressing the SELect key will move the
cursor (flashing character) one bit to the
left. That bit can then be be changed by
pressing the Increment/Decrement keys.