Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 141

Advertising
background image

5–31

Programming Parameters

Publication 1397-5.0 — June, 2001

ADV SETUP

[Pos Cur Lim Src] — P.069

Selects the source for the positive current
limit.

If Register is selected, the reference is [Pos
Cur Lim]
.

The I/O Expansion kit must be installed to
use Analog In 3 (terminals 50 and 51 on the
I/O Expansion board), Analog In 4 (terminals
52 and 53), or Frequency In (terminals 39,
40, and 41).

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Register
1 = Analog In 3
2 = Analog In 4
3 = Frequency In
4 = Adapter 1
5 = Adapter 2
6 = Adapter 3
7 = Adapter 4
8 = Adapter 5
9 = Adapter 6

Default Setting:

Register

Parameter Type:

Configurable

Group:

Advanced Set–Up

Factory Default:

0

Minimum Value:

0

Maximum Value:

9

[Neg Cur Lim Src] — P.070

Selects the source for the negative current
limit. If Register is selected, [Neg Cur Lim] is
used as the limit.

The analog input choices are only available if
the I/O Expansion kit is installed. The
Network choices are only available if the
Network Option kit is installed.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Register
1 = Analog In 3
2 = Analog In 4
3 = Frequency In
4 = Adapter 1
5 = Adapter 2
6 = Adapter 3
7 = Adapter 4
8 = Adapter 5
9 = Adapter 6

Default Setting:

Register

Parameter Type:

Configurable

Group:

Advanced Setup

Factory Default:

0

Minimum Value:

0

Maximum Value:

9

Note: Default is zero for non-regenerative drives, if [Feedback Type] is set to AC Tach, or if [Feedback Type] is set to Encoder and [Encoder
Quad]
is off.