Figure a.5 outer control loop, Firmware block diagrams a–5 – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 223

Advertising
background image

Firmware Block Diagrams

A–5

Publication 1397-5.0 — June, 2001

Figure A.5
Outer Control Loop

OCL Ref
Source
(P. 301)

*REGISTER

OCL Reference TP
(P. 020)

OCL Ramp
Output
(P. 019)

NOTES:
1>The –_oct_

enable signal must be

ON in order for the Outer Control
Loop to execute. When _ocl_ enable
is OFF, the S–curve Lead/Lag and PI
blocks are held in reset causing the
initial value (INITV) to be copied to
each block’s output.

2> The OCL reference ramp block
can be bypassed by setting OCL
RAMP TIME to 0.0.

*Indicates default selection

From
I/O Exp
Inputs Block
Diagram

+

MUL

OCL Reference
(P. 299)

ANLG IN 4

RATIO

OCL Enable TP
(P. 016)

*BYPASS

1> –OCL_enable
(to above)

FREQUENCY IN

ANLG IN 3

ADAPTOR 1–6

From SCANport

SCURVE

JERK

ACC

DEC

RST\

OCL Ref
Rounding
(P. 300)

OCL Trim
Range
(P. 302)

OCL
Output
(P. 018)

INTV

–OCL–enable
(from below)

2> Ramp Time
(P. 298)

OCL Pos
Limit
(P. 296)

OCL Kp
(P. 294)

OCL
Lead
Freq
(P. 295)

OCL
Neg
Limit
(P. 297)

LO

WLD

RST\

–OCL–
enable
(from below)

GAIN

INTV

KP

HI

OCL
Lead/Lag
Type
(P. 293)

LEAD/LAG

LAG/LEAD

OCL

Lead/Lag

Ratio

(P. 292)

–OCL–
enable
(from below)

OCL

Lead/Lag

Freq

(P. 293)

INTV

L/L

From
I/O Exp
Inputs Block
Diagram

(CML FEEDBACK)
8 sample average

ANLG IN 3

ANLG IN 4

CML FEEDBACK

FREQUENCY IN

From SCANport

OCL Fdbk
Source
(P. 290)

WLO

OCL Feedback
(P. 017)

Outer Control Loop enable logic

OCL ENABLE LOGIC

REGISTER

OCL Enable
(CTB 64)

ADAPTOR 1–6

REGISTER

TERMBLK

OCL Enable TP
(P. 016)

Drive
Status
(P. 191)

OFF

Running

Not Running

RST\

0

To
A.6

OCL Fdbk Reg
(P. 304)