5–22

Programming Parameters

Publication 1397-5.0 — June, 2001

SETUP

[CT Turns Ratio] — P.036

The drive current transformer turns ratio
(Tp/Tn).

See Regulator board replacement
instructions for information on determining the
CT TURNS RATIO. This parameter is not
restored if a Restore Defaults is done.

Display/Drive Units:

Tp/Tn

Parameter Type:

Configurable

Group:

Setup

Factory Default:

Value varies per HP rating (See table below)

Minimum Value:

1

Maximum Value:

32767

ATTENTION: The [CT Turns Ratio] parameter is also used in the
calculation of the burden resistor value. Do not adjust/change the value
of this parameter from its factory set value unless you are replacing the
regulator board (see chart below). Failure to observe this precaution
could result in damage to, or destruction of, the equipment.

!

The Drive Current Transformer Turns Ratio
(Tp/Tn):

Value to Enter

1.5 HP at 230 V AC/3 HP at 460 V AC

139

2-7.5 HP at 230 V AC/5-15 HP at 460 V AC

208

10-15 HP at 230 V AC/20-30 HP at 460 V AC

417

20-30 HP at 230 V AC/40-60 HP at 460 V AC

833

40-75 HP at 230 V AC/75-150 HP at 460 V AC

2000

100-150 HP at 230 V AC/200-300 HP at 460
V AC

5230

400–600 HP at 460VAC

7770

7 Amps at 380/415 VAC

139

29 Amps at 380/415 VAC

208

55 Amps at 380/415 VAC

417

110 Amps at 380/415 VAC

833

265 Amps at 380/415 VAC

2000

[Accel Time] — P.037

Amount of time it will take the drive to reach
[Max Motor Speed] from 0 speed. Smaller
changes in speed will take proportionately
less time.

In proportional trim mode, the actual time to
accelerate will be modified by [Draw Percent
Out]
.

Refer to the Speed Reference Ramp, Fig.
A.4
block diagram, for additional information.

Display/Drive Units:

SECONDS

Group:

Setup

Type:

Tunable

Factory Default:

5.0

Minimum Value:

0.1

Maximum Value:

300.0