Chapter

4

Publication 1397-5.0 — June, 2001

Start–Up and Adjustment

This chapter is a detailed step-by-step procedure for the proper start
up and tuning of the 1397 drive. Among the procedures to be
performed in this chapter are the following:

• Verify Wiring
• Verify proper supply voltages.
• Calibrate drive set-up parameters.
• Set jumper switches
• Execute drive tuning procedures.

The Start Up checklist should be used to record all data.

!

ATTENTION: Servicing energized industrial control
equipment can be hazardous. Severe injury or death
can result from electrical shock, burn, or unintended
actuation of controlled equipment. Hazardous voltages
may exist in the cabinet even with the circuit breaker in
the off position. Recommended practice is to
disconnect and lock out control equipment from power
sources, and discharge stored energy in capacitors, if
present. If it is necessary to work in the vicinity of
energized equipment, the Safety Related Practices of
NFPA 70E, “ELECTRICAL SAFETY FOR
EMPLOYEE WORKPLACES” must be followed.
DO NOT work alone on energized equipment!

!

ATTENTION: Potentially fatal voltages may result
from improper useage of an oscilliscope and other test
equipment. The oscilliscope chassis may be at
potentially fatal voltage if not properly grounded. If an
oscilliscope is used to measure high voltage
waveforms, use only a dual channel oscilliscope in the
differential mode with X-100 probes. It is
recommended that the oscilliscope be used in the A
minus B Quasi-differential mode with the oscilliscope
chassis grounded to an earth ground. Refer to
equipment safety instructions for all test equipment
before using with the 1397.