Programming Parameters

Publication 1397-5.0 — June, 2001

INPUT CONFIG

[Anlg In 1 Gain] — P.127

Used to scale the analog input 1 signal after it
has been conditioned by the drive hardware.
Typically, it will be 1.000.

Display/Drive Units:

Numeric

Parameter Type:

Tunable

Group:

Input Cong

Factory Default:

1.000

Minimum Value:

0.750

Maximum Value:

2.250

[Anlg In 1 Type] — P.128

Selects the analog input 1 signal type.

Note: Jumpers J10 and J12 must be set for
the same type of signal selected by this
parameter.

Display/Drive Units:

Numeric

Parameter Range:

0 = 0-10V
1 =

±10V

2 = 4 -20mA
3 = 10-50mA

Parameter Type:

Configurable

Group:

Input Config

Factory Default:

0

Minimum Value:

0

Maximum Value:

3

[Anlg In 1 Zero] — P.129

Used to remove any hardware introduced
offset from the analog auto reference signal.
Typically, it will be 0.

Display/Drive Units:

Numeric

Parameter Type:

Tunable

Group:

Input Config

Factory Default:

0

Minimum Value:

–200

Maximum Value:

200

[Anlg In 2 Gain] — P.130

Scales the manual mode analog reference
signal after it has been conditioned by the
drive hardware. Typically, it will be 1.000.

Display/Drive Units:

Numeric

Parameter Type:

Tunable

Group:

Input Config

Factory Default:

1.000

Minimum Value:

0.750

Maximum Value:

2.250