Figure 2.22 terminal strip inputs – Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 50

Advertising
background image

2–32

Installation

Publication 1397-5.0 — June, 2001

TB–03

STOP – This is a level sensitive signal that initiates a
Stop command (0 = Stop, 1 = Not Stop). The stopping
mode is determined by the [Stop Mode Type] (P. 115)
parameter. This input CANNOT be masked. Both the
customer interlock And Coast to Stop must be made for
the Drive to be READY.

Figure 2.22
Terminal Strip
Inputs

Regulator Board Terminal Strip Inputs

20

1

REV

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

ANLG REF 1

ANLG REF 2

21

22

23

+24V

Run

Stop

Jog

Reverse/Forward

Reference Select

+24V

Customer Interlock

Fault Alarm Reset

+24V

Brush Wear

Motor Thermostat

+24V

+24V Common

+10V (Isolated)

+

+

High Range

Low Range

Common

Coast-to-Stop

Analog Reference 2

Analog Tachometer In

PLC End

(Refer to Pub. 1397-5.0 for Additional Information)

Regulator Board Terminal Strip Software Configurable Output Connections

(Drive Contacts Shown In Unpowered State)

24

25

26

27

28

29

30

31

32

Analog Out 1

Analog Out Common

Analog Out 2

Run

Fault

Alarm

FWD

2

3

2> All customer interlock contacts
must be closed for drive operation.

3> The circuit breaker is supplied with
200-300 HP regenerative drives.
Note that if any other interlocks are
required for your application, they
must be connected in series with
the circuit breaker contact to the
customer interlock input.

*

*

*

*

*

*

*

*

*

*

*

*

= Required for initial startup and

operational checks.
Voltage must be present at these
points during operation.

Analog Reference 1

RUN/STOP

by user

contact

1

2

3

Analog Reference 2

24V Common

Advertising