4–21

Start–Up and Adjustment

Publication 1397-5.0 — June, 2001

IMPORTANT: Jumpers are read only on powerup, so power must be
cycled for a change to a jumper setting to be recognized by the
Drive.

To set the jumpers:

1. Remove power from the Drive. Remove the cover. Refer to

Chapter 3 for cover removal. You do need to remove the HIM
bracket.

2. The jumpers are located on the regulator board as shown in

Figure 4.9.

3. Change the jumper settings as described in the following

description and record them in the Final Setting column of
Table 4.G.

Table 4.G
Jumper and Adjustment Settings

Jumper/Adjustment

Default Setting

Calculated Setting

Final Setting

J15 (Regulator Type)

Speed

J16 (Program Protection)

Not Currently Used

J20 (Field Loss Detect)

Enable

J21 (Field Supply Jumper)

N/A

1

J19 (Analog Ref 2)

Pot

J14 (Tach V Range)

62

J11 (Tach V Scale)

16

J10 (Analog Ref 1)

Volts

J12 (Analog Ref 1)

Volts

J18 (ARM I FB RB)

Position 4

1

Only applicable when the optional Enhanced Field Supply kit is installed.

Setting the Regulator Type (Jumper J15)

J15 determines whether the Drive uses speed/voltage or
torque/current regulation mode. This jumper is read only when the
regulator is powered up.

When Current is selected, all speed references become torque
references. For example: Analog Ref 1 and Ref 2 are now Torque
References.

Also note that speed/voltage parameters must be set to provide
overspeed protection for the Drive.

!

ATTENTION: Failure to correctly set speed/voltage
parameters could result in dangerously high motor
speeds. Failure to provide overspeed protection could
result in bodily injury or equipment damage.