Programming Parameters

Publication 1397-5.0 — June, 2001

METERING

[Cur Loop Ref] — P.008

The amplitude and rate limited value of the
selected Current Loop Reference.

Display/Drive Units:

AMPS

Group:

Metering

Parameter Type:

Factory Default:

0

Minimum Value:

–1440

Maximum Value:

1440

[Draw Percent Out] — P.009

Determined by the selected trim reference
signal and [Trim Range] value. [Draw
Percent Out]
is used as a multiplier in the
proportional trim mode for accel and decel
rates. It is also used to generate the [Trim
Output]
value.

Display/Drive Units:

%

Group:

Metering

Parameter Type

Read Only – Output

Factory Default:

0

Minimum Value:

+/– 0.10

Maximum Value:

+/– 100.0

[Field Feedback] — P.010

Motor field current feedback signal after
scaling and gain. Used by the field current
regulator and field loss detection circuit.

Display/Drive Units:

AMPS

Group:

Metering

Parameter Type

Factory Default:

0

Minimum Value:

–0.0

Maximum Value:

20.0

[Frequency In] — P.011

Only used if the I/O Expansion kit is installed.
Gain adjustment for analog input 1 (terminals
50 and 51 on the I/O Expansion board).

The digital value of the frequency input
(terminals 39, 40, and 41 on the I/O
Expansion board). Freq In is scaled between
[Freq In Zero] and [Freq In Scale].

Display/ Drive Units:

kHz

Group:

Metering

Parameter Type

Factory Default:

0

Minimum Value:

–2000

Maximum Value:

2000

Freq In is zero when the frequency at the input is less than or equal to [Freq In Zero]. It is 4095 when the frequency equals [Freq In Scale].

Frequency In