Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 181

Advertising
background image

5–71

Programming Parameters

Publication 1397-5.0 — June, 2001

DIAGNOSTICS

[Alarm Reset] — P.197

Allows resetting of the fault or alarm through
the HIM.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Ready
1 = Reset

Parameter Type:

Read Only

Group:

Diagnostics

Minimum Value:

0

Factory Default:

0

Maximum Value:

1

Note: Analog input 2 (terminals 52 and 53 on the I/O Expansion board) only accepts a

±10 VDC input signal and cannot be changed.

[CPU Loading] — P.198

Shows the amount in % that the CPU is busy.
Should always display 100%.

Display/Drive Units:

%

Parameter Type:

Read Only

Group:

Diagnostics

Minimum Value:

0

Factory Default:

0

Maximum Value:

100

[Not Ready Cause] — P.199

Shows those inputs or conditions that cause
the Drive to remain “Not Ready”.
Bit#

Enum

0

Stop Asserted

1

TB Coast/DB

2

TB Interlock

3

Fault Active

4

Config Active

5

Field Perm

Display/Drive Units:

Numeric/Text

Parameter Type:

Read Only

Group:

Diagnostics

Minimum Value:

0

Maximum Value:

5

[ScanPort Errors] — P.200

The value of this parameter is incremented
everytime a SCANport message is not
received when expected from a peripheral
device. This value incrementing occasionaly
does not indicate a problem. The value will
change, if SCANport devices are removed or
reconnected to the drive. A value that is
consistently incrementing, over a period of
time, indicates a possible electrical noise
problem or malfunctioning peripheral
SCANport device.

Display/Drive Units:

%

Parameter Type:

Read Only

Group:

Diagnostics

Minimum Value:

0

Factory Default:

0

Maximum Value:

6500