5–59

Programming Parameters

Publication 1397-5.0 — June, 2001

OUTPUT CONFIG

[Dig Out 1 Src] — P.155

Only available if the I/O Expansion Kit is
installed.

Selects the signal that drives digital output 1
(terminals 66 and 67 on the I/O Expansion
board).

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Monitor 1 Out
1 = Monitor 2 Out
2 = In Current Limit
3 = Drive Ready

Parameter Type:

Configurable

Group:

Output Config

Factory Default:

0 [Monitor 1 Out]

Minimum Value:

0 [Monitor 1 Out]

Maximum Value:

3 [Drive Ready]

ATTENTION: This output is intended for use as an indication: DO
NOT use this as a control source. If it is used as a control source, a
dangerous condition can result. Failure to observe this precaution can
result in severe bodily injury or loss of life.

!

[Dig Out 1 Type] — P.156

Only used if the I/O Expansion Kit is installed.

Selects whether digital output 1 (terminals 66
and 67 on I/O Expansion board) is normally
open or normally closed.

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Normal Open
1 = Normal Closed

Parameter Type:

Configurable

Group:

Output Configuration

Factory Default:

0 [Normal Open]

Minimum Value:

0 [Normal Open]

Maximum Value:

1 [Normal Closed]

ATTENTION: On a power cycle or reset, the contact is held at normally
open until the drive software is initialized. Make sure that this condition
does not result in a dangerous situation for your application. Failure to
observe this precaution can result in severe bodily injury or loss of life.

!

If [Normal Open] is selected, digital output 1 is open when the signal is off and closed when it is on.

If [Normal Closed] is selected, digital output 1 is closed when the signal is off and open when it is on.