Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 172

Advertising
background image

5–62

Programming Parameters

Publication 1397-5.0 — June, 2001

OUTPUT CONFIG

[Freq Out Zero] — P.161

Only used if the I/O Expansion kit is installed.

The frequency generated when the signal
driving the frequency output is zero. If the
signal goes negative, the frequency output
maintains the frequency set by this
parameter.

Display/Drive Units:

kHz

Parameter Range:

2.0 to 250.0 kHz

Parameter Type:

Configurable

Group:

Output Config

Factory Default:

2.0 kHz

Minimum Value:

2.0 kHz

Maximum Value:

250.0 kHz

DIAGNOSTICS

[Last Stop Cause] — P.166

Identifies the source of the signal which
caused the most recent drive “stop”.

This parameter is Read Only

Display/Drive Units:

Numeric / Text

Parameter Range:

Bit #

Enum Text

0

External

1

Jog

2

Internal

3

Current Limit

4

Ramp

5

Coast

6,7

Not Used

8

Fault

9

TB Interlock

10

TB Coast / OB

11

M–Contactor

12–15

Not Used

Parameter Type:

Configurable

Group:

Diagnostics

Factory Default:

N/A

Minimum Value:

N/A

Maximum Value:

N/A

[Open SCR Sens] — P.167

Open SCR diagnostic sensitivity adjustment.
Unbalanced AC lines can cause load sharing
differences between SCRs. This parameter
should be increased to increase the tolerance
of SCR load sharing differences due to
unbalanced lines.

Display/Drive Units:

%

Parameter Type:

Tunable

Group:

Diagnostics

Factory Default:

0%

Minimum Value:

0%

Maximum Value:

100%