Rockwell Automation 1397 DC Drive Firmware 2.xx User Manual

Page 128

Advertising
background image

5–18

Programming Parameters

Publication 1397-5.0 — June, 2001

METERING

[OCL Enable TP] — P.016

The status of the outer control loop (OCL). Off
indicates the OCL is disabled or held in reset
(the drive is not running). On (Enabled)
means it is operating.

Display/Drive Units:

Enum Text

Group:

Metering

Type:

Read Only

Factory Default:

0

Minimum Value:

0 (Disabled)

Maximum Value:

1 (Enabled)

[OCL Feedback] — P.017

The feedback value of the outer control loop.
Refer to the [Outer Control Loop] (Fig. A.5)
block diagram for additional information.

Display/Drive Units:

CNTS

Group:

Metering

Factory Default:

0

Minimum Value:

–5120

Maximum Value:

5120

[OCL Output] — P.018

The output of the outer control loop in speed
units. This is the OCL trim that is applied to
the speed/voltage control loop. Refer to the
[Outer Control Loop] block diagram (Fig.
A.5) for additional information.

Display/Drive Units:

RPM

Group:

Metering

Factory Default:

0

Minimum Value:

–5000

Maximum Value:

5000

[OCL Ramp Output] — P.019

The outer control loop reference ramp output
in OCL user units. This is the OCL reference
output after OCL reference rounding and
S-curve have been applied. Refer to the
[OCL Ramp Time] block diagram for
additional information.

Display/Drive Units:

CNTS

Group:

Metering

Factory Default:

0

Minimum Value:

–4095

Maximum Value:

4095

[OCL Reference TP] — P.020

The value of the currently selected OCL
Reference Source.

Display/Drive Units:

CNTS

Parameter Type:

Read Only

Group:

Metering

Factory Default:

0

Minimum Value:

–4095

Maximum Value:

4095

Advertising