5–69

Programming Parameters

Publication 1397-5.0 — June, 2001

DIAGNOSTICS

[Logic Status] — P.190

Displays the logic condition. A typical value
at power up would be 0000000000000101
(i.e. drive is ready, not running, forward
direction commanded, no accel/decel, no
alarm, no fault etc.).
Bit

Definition

Status

0

Enabled

1=Enabled

1

Running

1=Running

2

Command Dir

1=Forward

3

Actual Direction

1=Forward

4

Acceleration

1=Accelerating

5

Deceleration

1=Decelerating

6

Warning

1=Warning

7

Fault

1=Faulted

8

At Ref (speed)

1=At Ref.

9–11 Local #
12–15 Reference *

Display/Drive Units:

Numeric/Text

Parameter Range:

Bit # Enum Text

Bit#

Enum Text

0 = Enabled

10 = Local ID

1 = Running

11 = Local ID

2 = Command Dir

12–15 = Reference ID

3 = Actual Dir
4 = Accelerating
5 = Decelerating
6 = Alarm
7 = Faulted
8 = At Speed
9 = Local ID

Group:

Diagnostics

Factory Default:

0

Minimum Value:

0

Maximum Value:

15

#
000 = Port 0 local
001 = Port 1 local
010 = Port 2 local
011 = Port 3 local
100 = Port 4 local
110 = Port 5 local
111 = Multiplexed

*
0000 = Master Ext Ref 1

1000 = Master Ext Ref 2

0001 = Int Ref 1 (Preset 1)

1001 = Port 1 Ext Ref

0010 = Int Ref 2 (Preset 2)

1010 = Port 2 Ext Ref

0011 = Int Ref 3 (Preset 3)

1011 = Port 3 Ext Ref

0100 = Int Ref 4 (Preset 4)

1100 = Port 4 Ext Ref

0101 = Int Ref 5 (Preset 5)

1101 = Port 5 Ext Ref

0110 = Int Ref 6 (Preset 6)

1110 = Port 6 Ext Ref

0111 = Int Ref 7 (Preset 7)

1111 = Int Jog

[Drive Status] — P.191

This parameter displays the actual operating
condition in text format

Display/Drive Units:

Numeric/Text

Parameter Range:

0 = Not Ready

4 = Tuning

1 = Ready

5 = Stopping

2 = Running

6 = Faulted

3 = Jogging

Group:

Diagnostics

Factory Default:

0

Minimum Value:

0

Maximum Value:

6

[AC Line Period] — P.192

Shows AC line as measured by the drive.

Display/Drive Units:

uSEC

Parameter Type:

Read Only

Group:

Diagnostics

Factory Default:

None

Minimum Value:

16,124

Maximum Value:

20833