Start–Up and Adjustment

Publication 1397-5.0 — June, 2001

Table 4.B
Motor Field Connections

Drive Terminal

F1 ( + )

F2 ( – )

Wire No

Motor Terminal

Power Application

!

ATTENTION: The following start-up procedure must
be performed with power applied to the Drive. Some
of the voltages present are at incoming line potential.
To avoid electric shock hazard or damage to
equipment, only qualified service personnel should
perform the following procedure. Throughly read and
understand the procedure before beginning. If an event
does not occur while performing this procedure, DO
NOT PROCEED. REMOVE POWER by opening the
branch circuit disconnect device and correct the
malfunction before continuing.

Apply power to the Drive. If you are using a HIM programming
device, the Drive will display the following screen for several
seconds during power-up.

Connecting . . .

IMPORTANT: If the Drive detects a fault, a statement relating to the
fault will be shown on the display. Record this information, remove
all power and correct the fault source before proceeding.

Drives without AC Line Disconnect

Apply the main power source feeding the Drive, and measure the
voltage present between terminals.
L1 and L2 (181 – 182)
L1 and L3 (181 – 183)
L2 and L3 (182 – 183)
Record the measurements in Table 4.C:

Power-On Checks