Enabling power supply management – H3C Technologies H3C S12500 Series Switches User Manual

Page 182

Advertising
background image

170

IMPORTANT:

After you remove a power supply, wait 30 seconds before installing it again. Otherwise, the power supply
might fail.

Enabling power supply management

With the power supply management function, the system monitors the available power and system loads

in real time. When the power module is about to be overloaded, and before hardware protection is

performed, the system takes protective measures, for example, sending a message or limiting power

supply to the interface cards. Power supply management applies to the following scenarios:

When you insert an interface card, if power supply management is not enabled, the system directly
provides power supply to the card. This might result in insufficient power supply and the system

stops power supply to the entire frame. If power supply management is enabled, the system

compares the maximum power consumption of the inserted interface card with the system available

power. If the former is not greater than the latter, the system provides power supply to the interface
card. Otherwise, the system uses the redundant power supplies. If the system still cannot provide

enough power, the system does not provide power supply to the interface card.

When the power supply is insufficient because a power supply fails or is removed, if power supply
management is not enabled, the system performs self hardware protection. If power supply

management is enabled, the system starts the redundant power supplies. If no redundant power

supply is available, the system starts self hardware protection.

Redundant power supplies are reserved for power supply backup. For example, if you insert three power

supplies, you can set one of them as a redundant power supply. With power supply management, the

system starts a redundant power supply automatically when a power supply fails or is removed, or when

power consumption increases. Use the display power-supply command to view the power supply of the
device.
If power supply management is disabled, the system does not reserve any redundant power supply. In

this case, you can also use the power-supply policy redundant command to configure the number of

redundant power supplies, and this configuration will take effect after power supply management is
enabled.
To enable power supply management:

Step Command

Remarks

1.

Enter system view.

system-view

N/A

2.

Enable power supply

management.

In standalone mode:
power-supply policy enable

In IRF mode:

power-supply policy enable

chassis chassis-number

Use either command.
Enabled by default.

3.

Configure the number of
redundant power supplies.

In standalone mode:
power-supply policy redundant

module-count

In IRF mode:

power-supply policy chassis

chassis-number redundant

module-count

Use either command.
By default, the number of

redundant power supplies
depends on the reserved power,

which you can display with the

display power-supply command.