Installing Equipment Interface

Module (if used)

If no Equipment Interface Module is used, skip to “Selecting

Thermostat Location” beginning on page 12.

NOTE: If an EIM is mounted inside a metal cabinet, such

as a commercial rooftop unit, it is recommended

to use a THM4000R1000 Wireless Adapter for

extended wireless range. Mount the Wireless

Adapter outside the metal cabinet and connect to

the ABCD terminals at the EIM. The Wireless

Adapter functions as a remote antenna for the

EIM. After it is wired to the EIM, it automatically

takes over as the antenna for RedLINK communi-

cation. For best RedLINK performance, avoid

mounting the Wireless Adapter above the roof

deck or outside the exterior walls.

NOTE: If you install more than one thermostat and EIM,

the EIMs must be at least 2 feet apart for best

RedLINK performance.

Fig. 8.

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before wiring.

The Equipment Interface Module (EIM) can be mounted

vertically on the HVAC equipment or on a wall in the equipment

room.

1. Mount the EIM near the HVAC equipment or on the

equipment itself. Use screws and anchors as appropriate

for the mounting surface..

2. To wire the EIM, strip 1/4” insulation, then insert wires

(see Fig. 9). For wiring diagrams, see “Wiring” beginning

on page 135.

Fig. 9.

Wiring 24 Vac Common

• Single-Transformer System—Connect the common side of

the transformer to the C screw terminal of the EIM. Leave

the metal jumper wires in place between R, RC, and RH.

• Two-Transformer System—Connect the common side of the

cooling transformer to the C screw terminal of the EIM.

Remove the metal jumper wire between RC and RH.

Connect the hot side of heating transformer to RH and leave

the jumper wire between R and RC and connect the hot

side of cooling transformer to R or RC.

Selecting Discharge and Return Air

Temperature Sensor Mounting

Locations

Refer to the guidelines below and Fig. 10–14 for mounting

locations of the Discharge and Return Air Temperature

Sensors.

Selecting Discharge Air Temperature

Sensor Mounting Location

1. Mount the Discharge Air Temperature Sensor on the

supply duct in a location where the air is mixed well.

Mount the Discharge Air Temperature Sensor out of sight

of the A-Coil/Heat Exchanger when possible. See Fig.

10.

2. When possible, mount the Discharge Air Temperature

Sensor upstream of a Steam Humidifier, a Fan Powered

Humidifier or a Dehumidifier that is ducted to the supply.

See Fig. 11–12.

3. If space does not allow a Discharge Air Temperature

Sensor upstream of a Steam Humidifier or Fan Powered

Humidifier, mount the Discharge Air Temperature Sensor

downstream of the Humidifier. See Fig. 11. When setting

the Delta T Limits (see “Set Delta T Limits” on page 90),

be sure to consider the affect that the humidifier has on

Delta T.

4. If a Bypass Humidifier is installed, mount the Discharge

Air Temperature Sensor downstream of the Bypass

Humidifier. See Fig. 13–14.

EIM

A

B

C

D

WIRELESS

ADAPTER

CONNECT

POWER

THM4000R

CONNECTED

WIRELESS SETUP

MCR32389

R
C

Y
Y2

G
L

W O/B

W2 AUX1

W3 AUX2