THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

34

3080,

3090

Staging Control -

Backup Heat

Differential Stage 1

Note: “Stage 1" is

not displayed if

there is only 1

stage of Backup

Heat.

Comfort
2.0° F to 15.0° F from setpoint (in

0.5° F increments)

Comfort

Both

No

A backup heat differential can be set on any

system that has more than one heating

equipment type.

See “Backup Heat Differential (Droop)”

beginning on page 98.

The Comfort setting is only available on

systems when the Backup Heat Type is

Allowed to Run with the Primary Heat (Heat

Pump). For example, Heat Pumps with

Electric Forced Air Backup Heat.

The Comfort setting is NOT available for

Dual Fuel systems. For example, Heat

Pumps with Gas Forced Air.

3080,

3090

Staging Control -

Backup Heat

Differential Stage 2

Comfort
2.0° F to 15.5° F from setpoint (in

0.5° F increments)

Comfort

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

Backup Heat Differential Stage 2.

This ISU is only displayed if there are 2

backup heat stages.

The indoor temperature must drop to the

selected differential setting before the

thermostat will turn on backup heat stage

2. For example, if backup heat stage 2 is set

to 2° F (1.0° C), the indoor temperature

must be 2° F (1.0° C) away from the

setpoint before backup heat stage 2 turns

on. When set to Comfort, the thermostat

will use backup heat stage 2 as needed to

keep the indoor temperature within 1° F

(0.5° C) degree of the setpoint.

3110

Backup Heat

Upstage Timer

Off
(30, 45, 60, 75, 90) minutes
(2, 3, 4, 5, 6, 8, 10, 12, 14, 16)

hours

Off

Both

No

The Backup Heat Upstage Timer starts

when the highest stage of the previous

heating equipment type turns on. Backup

heat will be used (if needed) when the timer

expires. See “Backup Heat Upstage Timer”

beginning on page 99.

This ISU is only displayed when Backup

Heat Differential Stage 1 is set to 2 F or

higher (ISU 3080, 3090).

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes