Specifications – Honeywell PRESTIGE THX9321 User Manual

Page 3

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

3

68-0311—02

SPECIFICATIONS

Thermostat Description:

Electrical Ratings for:

Equipment Interface Module and the THX9321 Prestige 2.0

Thermostat

NOTE: To find what terminals are available on the Equip-

ment Interface Module and the Prestige Thermo-

stats, see “Terminal Designations” below the

table.

Terminal Designations:

— Equipment Interface Module: R, RC, RH, C, W-O/B,

W2-AUX 1, W3-AUX 2, Y, Y2, G, A-L/A, U1 U1, U2 U2,

U3 U3, S1 S1, S2 S2, S3 S3, S4 S4, A, B, C, D

— THX9421 Thermostat: R, C

— THX9321 Thermostat: R, RC, C, W-O/B, W2-AUX/E, Y,

Y2, G, A-L/A, K, U1 U1, U2 U2

Power Consumption of THX9421/THX9321:

Full brightness = 3.0 VA

1/2 brightness = 2.1 VA

Backlight off = 1.9 VA

RedLINK Communication:

Frequency: 900 Mhz frequency range

Re-Sync Time: RedLINK devices re-establish communication

within 6 minutes after AC power resumes.

Temperature Setting Range:

Heating: 40 to 90 °F (4.5 to 32 °C).

Cooling: 50 to 99 °F (10 to 37 °C).

Temperature Sensor Accuracy: ± 1.5 °F at 70 °F (0.75 °C at

21.0 °C)

Humidification Setting Range:

10% to 60% RH.

Dehumidification Setting Range:

40% to 80% RH.

Humidity Display Range:

0% to 99%.

Humidity Sensor Accuracy: ± 5% RH from 30% to 50% RH

at 75 °F (24 °C).

Cool Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Cool On” when the

thermostat turns the cooling on.

Heat Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Heat On” when the

thermostat turns the heating on.

Auxiliary Heat Indication:

Prestige 2.0 and Prestige IAQ 2.0 displays “Auxiliary Heat On”

when the thermostat turns the auxiliary heat on.

Interstage Differential:

Comfort: The thermostat keeps the indoor temperature within 1

degree of the setpoint (droop less control). The thermostat

turns on stage 2 when the capacity on stage 1 reaches

90%.

When the interstage differential is set to 1.0 or higher, the ther-

mostat stages the equipment based on how far the indoor

temperature is from the setpoint (ISU 3030 to 3090). See

page 31 for more information.

Clock Accuracy: ± 1 minute per month at 77 °F (25 °C). ± 2

minutes per month over the operating ambient temperature

range.

Mounting Means:

Thermostat mounts directly on the wall in the living space

using mounting screws and anchors provided. Fits a hori-

zontal 2 x 4 in. junction box.

Equipment Interface Module (EIM) mounts on HVAC equip-

ment or on a wall in the equipment room.

Feature

Description

Powering method

Common wire only

System types (up to

4 heat/2 cool heat

pump and up to 3

heat/2 cool

conventional)

Gas, oil or electric heat with air

conditioning

Warm air, hot water, high-efficiency

furnaces, heat pumps, steam and

gravity

Cool only

Changeover

Manual or Auto changeover selectable

System setting

Em Heat-Heat-Off-Cool-Auto

Fan setting

Auto-On-Circ-Follow Schedule

Terminal

Voltage

(50/60 Hz)

Max. Current

Rating

W - O/B

18 to 30 VAC and

750 mVDC

1.00A

Y (cooling)

18 to 30 VAC

1.00A

G (fan)

18 to 30 VAC

0.50A

W2 - Aux 1 (heating)

18 to 30 VAC

0.60A

W3 - Aux 2 (heating)

18 to 30 VAC

0.60A

Y2 (cooling)

18 to 30 VAC

0.60A

A-L/A (Output)

18 to 30 VAC

1.00A

U1, U1

U2, U2

U3, U3

18 to 30 VAC

0.50A