THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

88

7. Delta T Diagnostics is only for non-zoned forced air

systems.

8. The thermostat does not provide Heat or Cool Delta T

Diagnostics when it is set to control an Economizer

module (ISU 2220).

9. The thermostat cannot be setup for Heat Delta T

Diagnostics when the thermostat is used with an external

fossil fuel kit (ISU 2190).

Setting up Alerts and Diagnostics

1. Set up the Return and Discharge Air Sensors by

selecting the check boxes on the screen. These sensors

are used to measure Delta T.

Fig. 148.

2. Select the terminals that are wired to the Discharge and

Return Air Sensors (terminals S1, S2, S3, or S4 at the

EIM).

IMPORTANT

Be sure to select the correct terminals for the dis-

charge and return air sensors. For example, if the

return air sensor is wired to S1, select S1 (see Fig.

149) for the return air sensor.

Fig. 149.

3. Select the Discharge and Return Air Sensor Type (10K).

IMPORTANT

10K sensors must be used for Delta T Diagnostics.

Fig. 150.

4. Turn on the Heat and Cool Delta T Diagnostics. Default

is On.

Fig. 151.

Fig. 152.