Honeywell PRESTIGE THX9321 User Manual

Page 39

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

39

68-0311—02

3150

Heat Cycles Per

Hour - Stage 3

Note: Depending

on the application,

the text displayed

on the screen may

show the specific

heating equipment

type.

1 to 12 CPH

Default varies

based on

heating

equipment type

selected

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

cycle rate.

This ISU is only displayed when ISU 2070

Heat Stages is set to 3 stages.

Cycle rate limits the maximum number of

times the system can cycle in a 1 hour

period measured at a 50% load. For

example, when set to 3 CPH, at a 50% load,

the most the system will cycle is 3 times

per hour (10 minutes on, 10 minutes off).

The system cycles less often when load

conditions are less than or greater than a

50% load. The thermostat automatically

defaults to the recommended cycle rate

based on the heating equipment type that is

used. You can change the cycle rate as

needed. Defaults for commonly used

systems are shown below.

Standard Efficiency Gas Forced Air = 5 CPH

High Efficiency Gas Forced Air = 3 CPH

Oil Forced Air = 5 CPH

Electric Forced Air = 9 CPH

Hot Water Fan Coil = 3 CPH

Hot Water Radiant Heat = 3 CPH

Geothermal Radiant Heat = 3 CPH

Steam = 1 CPH

Gravity = 1 CPH

3160

Backup Heat Cycles

Per Hour - Stage 1

Note: “Stage 1" is

not displayed if

there is only 1

stage.

1 to 12 CPH

Default varies

based on

heating

equipment type

selected

Both

No

ISU 3010 Temperature Control Options

must be set to Advanced to view or adjust

cycle rate.

This ISU is only displayed when ISU 2070

or 2130 Backup Heat Stages is set to 1

stage.

Cycle rate limits the maximum number of

times the system can cycle in a 1 hour

period measured at a 50% load. For

example, when set to 3 CPH, at a 50% load,

the most the system will cycle is 3 times

per hour (10 minutes on, 10 minutes off).

The system cycles less often when load

conditions are less than or greater than a

50% load. The thermostat automatically

defaults to the recommended cycle rate

based on the heating equipment type that is

used. You can change the cycle rate as

needed. Defaults for commonly used

systems are shown below.

Standard Efficiency Gas Forced Air = 5 CPH

High Efficiency Gas Forced Air = 3 CPH

Oil Forced Air = 5 CPH

Electric Forced Air = 9 CPH

Hot Water Fan Coil = 3 CPH

Hot Water Radiant Heat = 3 CPH

Geothermal Radiant Heat = 3 CPH

Steam = 1 CPH

Gravity = 1 CPH

Table 4. Installer Setup (ISU) Table. (Continued)

ISU

Number

Installer Setup

Name

Settings

Default

Residential,

Commercial

or Both

Requires

EIM

Notes