Economizer Module Wiring Diagrams

Typical wiring of a W7220 Economizer Module for a heat pump system, using a Prestige THX9321 thermostat or Equipment

Interface Module.

Fig. 346. Wiring a W7220 Economizer Module for a heat pump system.

Typical wiring of a W7220 Economizer Module for a conventional system, using a Prestige THX9321 thermostat or Equipment

Interface Module.

Fig. 347. Wiring a W7220 Economizer Module for a conventional system.

1 “A” or “L/A” terminal must be configured for Economizer in the installer setup (ISU 2220). These terminals are powered by the

cooling transformer (Rc terminal).

2 Terminal AUX 2 is present only on the Equipment Interface Module.
3 Connect the changeover valve from the roof top unit to the normally open contacts of an isolation relay to prevent feedback into

the economizer module during defrost. If this is not done when the system goes into defrost, it will change the economizer into

cooling mode due to the feedback and open the outside damper while in heating mode.

120

VAC

O/B

Y1

Y2

AUX AUX 2

G

24

VAC

AUX2-I

OCC

E-GND

AUX1-O

Y2-I

Y2-O

Y1-I

Y1-O

C

R

Rooftop Unit

Transformer

O/B

L/A

Y

Y2

AUX AUX 2

G

Thermostat/EIM

R

C

W7220 Economizer Module

(See wiring guidelines provided with the product)

2

1

MCR34808

3

3

1

120

VAC

Y1

Y2

W1

W2

G

24

VAC

Rooftop Unit

Transformer

A

Y

Y2

W

W2

G

Thermostat/EIM

R

C

W7220 Economizer Module

(See wiring guidelines provided with the product)

1

MCR34810

AUX2-I

OCC

E-GND

AUX1-O

Y2-I

Y2-O

Y1-I

Y1-O

C

R