Thx9321 prestige, Iaq with eim – Honeywell PRESTIGE THX9321 User Manual

Page 144

Advertising
background image

THX9321 PRESTIGE

®

2.0 AND THX9421 PRESTIGE

®

IAQ WITH EIM

68-0311—02

144

Fig. 332. Geothermal radiant heat with geothermal forced air and backup heat using separate transformer for the radiant

heat.

1 U1, U2 or U3 terminals must be used for geothermal radiant heat (ISU 2010). Thermostat allows 2 stages of radiant heat—geo-

thermal (stage 1) and boiler (stage 2).

2 “U” terminals are normally open dry contacts when set up for geothermal radiant heat. You must install a field jumper if radiant

heat is powered by system transformer. Do NOT install a field jumper if radiant heat has its own transformer.

3 L/A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD.

See “Economizer Module Wiring Diagrams” beginning on page 151.

4 Y2 used with heat pumps that have 2 compressor stages.

NOTE: For setup and operation, see “Geothermal Radiant Heat” beginning on page 100.

O/B

AUX1

AUX2

O

W1

W2

Y

Y2

G

R

C

O

Y

Y2

R

C

TRANSFORMER

24

VAC

120

VAC

L/A

TO THERMOSTAT

THERMOSTAT/EIM

HEAT PUMP

FURNACE

HEAT PUMP

M34525

RADIANT HEAT

ZONE MODULE

VALVE

PUMP

END SWITCH

C

R

3

4

1